I. Summary
IA IM series Remote control of intelligent electric actuator is the excellent product in the world. It provide the perfect functions, the best performance, light and the nice contour, adjustment simply, operation conveniently by using advantage super large scale digital integrated chip and special digital torque sensor and digital Hall sensor and operation in order.
To combine with valve become the unit of electric actuator, it is widely used for such automatic control systems as power, oil, gas, steel work, chemical factory, water and waste treatment. It not only meet requirement of of the modulating control frequently, but also suit to meet with regulated control.
The products have built in accordance with the standard:
Q/TK01-2011<<Remote control of intelligent electrical actuator>>,
Q/ZTK 02-2013<< Intelligent Electric Actuator Infra-red remote debugger>>,
GB3836.1-2010<<Explosive Atmospheres Part 1: Equipments General requirements for >>, <<GB3836.2-2010 Explosive Atmospheres- Part 2: Equipment protection by flameproof enclosures "d">>.
1. Main Features:
*Using the super large scale integrated chips, powerful functions, high precision.
*Designing with Electromechanical integration , nice contour and light weight.
*Available special pressure sensor can be measure the torque value of the output shaft. Rising the testing accuracy of the torque value and enable display and monitor alternately. Torque tripped, stalled can be shown and alarmed.
*Using hall sensor as the position transducer, detect the position, the pulse signals can be processed. Locating accuracy of the valve position is up to 1.0%.
*By using the non-intrusive infra-red setting tool set up the functions and parameters, adjusting and operating the actuator in local.
*Display in symbol and operating in order and it is easy to understand, view and operating.
2. The Description of the Function
*The protect function of the stroke limited.
*The protect function of the torque limited.
*The functions of the indication contacts.
1) Intermediate position 2) Opening 3) Closing 4)Running
5)Local stop 6)Local control 7)Remote control 8)Open interlock
9)Close interlock 10)Handwheel operating 11)Torque trip when opening
12)Torque trip when closing 13)Toque trip when running
*The Function of the Valve Alarm
1)Torque trip alarm a. Torque trip when closing b. Torque trip when opening
2)Stalled alarm a. Close stalled b. Open stalled
*The Function of the Control Alarm and Protect
1) ESD
2) Signal lost
*The Function of the Actuator Alarm and Protect
1) Overheating 2) Overheating in control box 3) Battery low 4) 24V error alarm
5) Phase lost 6) Sign lost 7) Inner communication error alarm8) Local module error
*The Protect Function of the Inverse run
*The Function of Push to Run / Self-Maintained Local Control
*The Choice Function of the Contact Type
*The Protect Function of the External Interlock
*The Protect Function of the Conditional Control
*The Function of the Two-Wire Control
*The Function of the Torque Bypass
*The Function of the ESD override protection
*The Function of the Interrupt Setting
*The Function of the Extra Indication Contacts
*The Function of the Infra-red Setting Tool
*The Function of the LED Display
*The Function of the Automatic Discriminant of Phase sequence
II Types and Specifications
According the displacement of the output shaft, the actuator can be described as following:
a) Multi-turn remote control of intelligent electric actuator
b) Linear stroke remote control of intelligent electric actuator
c) Quarter turn remote control of intelligent electric actuator
According the duty, rate, circle, the actuator can be described as following:
a) IA series Remote control of intelligent electric actuator(S2, 25%, ≤630 starts per hour)
b) IM series Remote control of intelligent electric actuator(S2, 25%, ≤630 starts per hour ≥1200 starts per hour)
The actuator types:
1) IA series multi-turn remote control of intelligent electrical actuator
2) IM series multi-turn modulating remote control of intelligent electrical actuator
3) IML series linear stroke modulating remote control of intelligent electrical actuator
4) IA/Mow quarter turn series remote control of intelligent electrical actuator
5) IM/Mow quarter turn series modulating remote control of intelligent electrical actuator
III Main Technical Parameters
* Input signal: 1) Analogue signal a. 4-20mA. DC input resistance 250Ω
b. 0-10mA. DC input resistance≤750Ω
* Output Shaft Torque, Speed, Stroke, Time as shown: table
* The Consumed Power of the remote control of intelligent electric actuator as shown: table
* Accuracy:
1) IA, IM Multi-turn remote control of intelligent electric actuator ≤±1% 2) IA/Mow, IM/Mow quarter turn series remote control of intelligent electric actuator ≤±1%
3) IML series linear stroke modulating remote control of intelligent electric actuator ≤±1% (stroke ≥25mm)
* Control Deadband: 0.1~9.9% adjusting, default setting ≤0.5%
* Limited in Midway: Opening Limited 40%~100%
Closing Limited 0%~60%
* Clearance:
1) IA series multi-turn remote control of intelligent electric actuator ≤1º
2) IM series multi-turn modulating remote control of intelligent electric actuator ≤1º
3) IML series linear stroke modulating remote control of intelligent electric actuator ≤1mm
4) IA/Mow quarter turn series remote control of intelligent electric actuator ≤1º
5) IM/Mow quarter turn series modulating remote control of intelligent electric actuator ≤1º
* Inhibit Operating Times: 0~99 seconds adjusting
* Power Supply:
*Power Supply: Single Phase AC: 220V
Three Phase AC: 380V, 400V
Frequency: 50/60Hz(±1%)
(*lease connect us for special power supply)
* Enclosure: IP68
* Explosion Proof:
1) Setting tool Exia II CT4
2) electrical equipment Exd II BT4,Exd II CT4
* Contact Capacity: 250V AC, 5A; 30V DC, 5A
* Ambient:
1) Ambient temperature: -25ºC~+70ºC (Explosion Proof -20ºC~+60ºC)
2)RH: 5%~98%
3) Atmosphere pressure: 86 ~ 106kPa
4) Air medium: non-caustic
* Interference Performance:
a) Magnetic field immunity: ≤400A/m, 50Hz
b) Common mode interference: 250V, 50Hz
c) Differential mode interference: 1V, 50Hz, 0~360º
d) Electrostatic discharge: 4kV
e) Electrical fast transient burst: power supply terminal 1000V; input signal terminal 500V
f) Radio-frequency electromagnetic field immunity: frequency 80~100MHz field intensity
3V/M distance 1m
g) Surge immunity 1kV
IM/Mow series quarter turn modulating intelligent electric actuator Voltage 380V 50Hz, 90º
No | Type | Torque(N.M) | Time (S) | | No | Type | Torque(N.M) | Time (S) |
1 | IM10/MOW3-40 | 225 | 33 | | 10 | IM20/MOW5-70 | 1400 | 44 |
225 | 25 | 11 | IM20/MOW6-70 | 1440 | 58 |
210 | 17 | 1440 | 44 |
180 | 13 | 1200 | 29 |
2 | IM10/MOW3-60 | 300 | 58 | 960 | 22 |
300 | 44 | 12 | IM18/MOW6R-140 | --- | --- |
270 | 29 | 1730 | 88 |
240 | 22 | 13 | IM20/MOW6R-140 | 2600 | 116 |
3 | IM12/MOW4-40 | 450 | 33 | 2600 | 88 |
450 | 25 | 2200 | 58 |
400 | 17 | 1750 | 44 |
360 | 13 | 14 | IM25/MOW7-60 | 3000 | 50 |
4 | IM12/MOW4-70 | 600 | 58 | 3000 | 38 |
600 | 44 | 2500 | 25 |
550 | 29 | 2000 | 19 |
475 | 22 | 15 | IM35/MOW7-60 | 5880 | 38 |
5 | IM18/MOW4-40 | --- | --- | 3950 | 19 |
725 | 25 | 3950 | 13 |
6 | IM12/MOW5R-80 | 825 | 66 | 16 | IM20/MOW7R-180 | 4500 | 150 |
825 | 50 | 4500 | 113 |
740 | 34 | 3800 | 75 |
660 | 25 | 3000 | 56 |
7 | IM18/MOW5-70 | --- | --- | 17 | IM25/MOW8R-180 | 8450 | 150 |
950 | 44 | 8450 | 113 |
8 | IM20/MOW5-40 | 1100 | 33 | 7150 | 75 |
1100 | 25 | 5650 | 56 |
910 | 17 | 18 | IM35/MOW9R-180 | 16200 | 150 |
725 | 13 | 16200 | 113 |
9 | IM12/MOW5R-120 | 1200 | 100 | 15200 | 75 |
1200 | 75 | 12200 | 56 |
1100 | 50 | | | | |
980 | 38 | | | | |